Air Control PRO Signal

It's a matter of quality: Air Control

In addition to managing light, some of our presence detectors also provide the capability of controlling heating, ventilation, air-conditioning in relation to whether or not persons are present. This makes a lot of sense from an energy point of view as it can save large quantities of it: If nobody's there, why keep the heating on all the time.

Yet, gradually, another aspect's creeping into the focus of discussion: air quality or the content of CO2 in room air. Ventilation systems require energy and the air that's exchanged needs either heating or cooling. But the mere presence of persons is not enough for air to be exchanged through a ventilation system or automatically controlled window. What's important is the quality of air.

People inhale O2 and exhale CO2. This is a situation everyone's familiar with: as the meeting wears on, concentration lapses and, at some point everybody's tired, and later on people start to get a headache. The reason for this is the content of CO2 in room air. Unfortunately, this is something people only notice when it's far too late to remedy the situation and actively provide ventilation. This is where our Air Control sensor comes in - because it measures the amount of CO2 that's present in room air.

AC PRO Signal

  • Air-quality sensor matching presence detector
  • High energy-saving potential from on-demand ventilation
  • Automatic, maintenance-free CO2 measurement
  • Controls air-conditioning (ventilation, window opening, co-ordinated heating control etc.)
  • Provides information on air quality and the need for fresh air (visually and acoustically)
  • Also suitable for retrofi tting in training, conference, classrooms, offi ces and the home
  • Acoustic warning every 5 min. above 1500 ppm (can be deactivated)
  • Self-calibrating (to fresh air and air pressure/altitude)
  • Indicator with 3 LED's
    (green, amber, red) Green: < 1000 ppm
    (light 'ON' permanently, can be switched 'OFF') Orange:1000 ppm – 1500 ppm
    (light 'ON' permanently) Red: > 1500 ppm (fl ashing)

AirControlPRO_01en.jpg

             AirControlPRO_02.jpg


AC PRO Signal
EAN Signal UP
(surface-mounting)
EAN Signal AP
(concealed)
4007841 592608

4007841 592707

Dimensions
(w x h x d)
AC PRO Signal UP 120 x 120 x 53 mm
AC PRO Signal AP 120 x 120 x 49 mm
Voltage
230 VAC
CO2 measurement range
400 – 2000 ppm
CO2 accuracy
5% of measurement reading ± 150ppm
(at 25°C and 1013 hPa)
Indicated by LEDGreen: up to 1000 ppm (light 'ON' permanently,
can be switched 'OFF')
Amber: from 1000 ppm CO2 to 1500 ppm CO2,
(light permanently 'ON')
Red: over 1500 ppm CO2 (fl ashing)
Acoustic warning signal: every 5 min. above 1500 ppm
CO2, can be switched 'OFF'
Temperature
dependence of CO2
< 5 ppm per °C
Temperature (storage)
- 40°C to + 70°C
Relay (function)
Relay ON from 1200ppm
Relay OFF under 800ppm
(with falling CO2 concentration)
Response time (T90)
5 min
Signal output
Contact Typ: 1,3
Housing
Standardised concealed box
IP rating
IP 20 (shock hazard protection for indoors)
Safety class
II

Subject to technical modifications.

CO2 meas. range
CO2 measurement range 400 – 2000 ppm with an accuracy of +/- 150 ppm

Controls
The LED traffi c-light logic indicates the quality of room air